Power distribution cables in power stations, industrial installations and switchgears, as well as in local mains. For fixed installation undergroud, in interior premises, cable ducts, in open air, in water – as permited by the local building regulations – under severe mechanical stressing during installation and operation.
E-AY2Y Cable Standard
HD 603 S1, IEC 60502-1, ÖVE E8200-603 CONSTRUCTION :
E-AY2Y Cable Construction
1.Conductor - Aluminium conductor class 1 or class 2 2.Insulation - Core insulation of polyvinylchloride (PVC) 3.Filling - PVC core covering (FM) or taping (BD) 4.Outher sheath - Polyethylene (HDPE), Black, UV resistant TECHNICAL : Electrical Performance:
Nominal Voltage: 600/1000 Volt Test Voltage [V]AC 4000 Short circuit time max. [sec] 5 Bending radius: x diameter 15
Temperature range: Min. temp. for cable laying: -5°C Max. working temperature: 70°C Max. short-circuit temperature: 160°C
Min. bending radius: single-core – 15D; multicore – 12D Flammability: Reaction to fire EN 60332-1-2 - Eca PARAMETER :