1.Executive Standard
PV cable(solar cable) refers to original draft made out by PV system cable work team of German Standard Committee(Technical Specification 2PFG1169/08.2007 in Rhein TUV company German).
2.No-haogen PV-Cable Type
PV1-F: Tinned Flexible Copper Wire No Halogen PO Insulation&Sheath Photovoltaic System Cable.
3. Application
Applied to solar panels for power generation and related components of the wiring, connection,particularly suitable for outdoor . Resistance to sunlight, anti-aging , Using the low smoke halogen-free flame retardant materials, higher grade, more safety .
4.Cable Characteristics
Conductor | Tinned copper,according to VDE0295/IEC60228,class 5 |
Outer sheath | Polyolefin copolymer electron-beam cross-linked |
Rated voltage | AC Uo/U=1000/1000VAC,1500VDC |
Voltage test on finished cable | 6.5kV AC,15kV DC,5min |
Ambiet temperature | (-40°C up to +90°C) |
Conductor maximum temperature | +120°C |
Service life | >25years(-40°C up to +90°C) |
The permitted short-circuit-temperature refer to a period of 5s is+200°C | 200°C ,5 seconds |
Bending radius | ≥4xϕ (D<8mm) |
| ≥6xϕ (D≥8mm) |
Acid and alkali resistance test | EN60811-2-1 |
Cold bending test | EN60811-1-4 |
Damp heat test | EN60068-2-78 |
Sunlight resistance | EN60811-501,EN50289-4-17 |
O-zone resistance test of finished cable | EN50396 |
Fire test | EN60332-1-2 |
Smoke density | IEC61034,EN50268-2 |
Assessment of halogens for all non-metallic material | IEC670754-1 EN50267-2-1 |
5.PV1-F Structure Parameter
Cross section (m㎡) | construction (No./mm) | Conductor Stranded OD.max(mm) | Cable OD. (mm) | Max Cond Resistance (Ω/km,20ºC) | Current carring Capacity AT 60ºC(A) |
|
|
|
1.5 | 30/0.25 | 1.58 | 4.9 | 13.7 | 30 |
2.5 | 49/0.25 | 2.02 | 5.4 | 8.21 | 41 |
4 | 56/0.285 | 2.5 | 6.1 | 5.09 | 55 |
6 | 84/0.285 | 3.17 | 7.2 | 3.39 | 70 |
10 | 84/0.4 | 4.56 | 9 | 1.95 | 98 |
16 | 128/0.4 | 5.6 | 10.2 | 1.24 | 132 |
25 | 192/0.4 | 6.95 | 12 | 0.795 | 176 |
35 | 276/0.4 | 8.74 | 13.8 | 0.565 | 218 |