• PRODUCTS

ACSR Beaver Conductor 70mm2

Aluminum Conductor Steel Reinforced ACSR Beaver Conductor 70mm2

Code name: Beaver

Corss section area: 70mm2

Standard: BS 215 Part 2

Conductor Material: Aluminum and Steel
Phone: +8613204662621
WhatsApp: +8613204662621
E-mail: yongbencable@163.com
Contact Us

- // PRODUCT DETAILS // -


ACSR Beaver Conductor 70mm2 Application:


ACSR – The full name: Aluminum Conductor Steel Reinforced. Aluminum Conductor Steel Reinforced is used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
FEATURES :

ACSR Beaver Conductor 70mm2 Features:

With simple structure, the aluminum conductor steel reinforced is easy to set up and maintain, with low cost and high transmission capacity. It is advantageous for this ACSR to be put up across a valley or river or under other various special geographic conditions. The ACSR has advantages of sound electrical conductivity, high mechanical strength, high tensile strength, etc, and the pole distance can be lengthened. It is used for power transmission lines with various voltage levels and plays an important role in the electricity transmission field.

CONSTRUCTION :

ACSR Beaver Conductor 70mm2 Construction:

Form the name, we can know the acsr beaver conductor is aluminum conductor steel reinforced. acsr beaver conductor belongs to BS-215 standard, which is British standard. “Beaver” is a code name of acsr conductor. ACSR beaver conductor is a special type of stranded cable that consists of steel core surrendered by aluminum. So we can see its structure is very simple.The specification of mink conductor is 6/3.99mm aluminum and 1/3.99mm steel. And the high tensile strength and hardness of steel core ensure the weather-resistance property and the long span. From the calculation, the total linear mass should be 302 kg/km. After the cabling, the calculated breaking should be 2570daN. . At 20℃, the calculate D.C. resistance is 0.0.3825 Ω/km. This is the basic beaver conductor size.


PARAMETER :

ACSR Beaver Conductor 70mm2 Parameter

Code nameacsr beaver conductor
Nominal aluminum area mm 270
Stranding structureAl. No.6
Al. Dia.3.99
St. No.1
St. Dia3.99
Sectional area of aluminummm 274.82
Total sectional areamm 287.29
Overall diametermm11.97
Total Weightkg/km302
Calculated breaking loaddaN2570
Calculate D.C resistance at 20 ℃Ω/km0.3825