Cable Application:
This standard applies of supported spacer cable. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer.
Stansards
● ICEA S-66-524 Cross-Linked-Thermosetting-Polyethylene-Insulated Wire and Cable for The Transmission and Distribution of Electrical Energy
● GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
Cable SAC Aluminum Spaced Aerial Cable Construction
The conductors are stranded,circular compressed aluminum. The conductor screen is the extruded Semi-conducting conductor shield in Black. The inner Insulation is mainly natural color thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black or Grey with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.15kV SAC Cable
| Nominal Size | Min. No. of Wires | Covering Thickness | Cable Diameter | Min. Breaking Load | Weight |
| Conductor Shield | Inner Layer | Outer Layer |
| mm² | No. | mm | mm | mm | mm | N | kg/km |
| 3-Layer 15kV AAC/XLPE/HDPE |
| 25 | 6 | 0.60 | 1.91 | 1.91 | 15.2 | 3762 | 221 |
| 35 | 6 | 0.60 | 1.91 | 1.91 | 16.2 | 5177 | 261 |
| 50 | 6 | 0.60 | 1.91 | 1.91 | 17.3 | 7011 | 310 |
| 70 | 12 | 0.60 | 1.91 | 1.91 | 19.0 | 10354 | 390 |
| 95 | 15 | 0.60 | 1.91 | 1.91 | 20.8 | 13727 | 486 |
| 120 | 15 | 0.60 | 1.91 | 1.91 | 22.0 | 17339 | 568 |
| 150 | 15 | 0.60 | 1.91 | 1.91 | 23.7 | 21033 | 664 |
| 185 | 30 | 0.60 | 1.91 | 1.91 | 25.3 | 26732 | 785 |
| 240 | 30 | 0.60 | 1.91 | 1.91 | 27.6 | 34679 | 973 |
25kV SAC Cable
| Nominal Size | Min. No. of Wires | Covering Thickness | Cable Diameter | Min. Breaking Load | Weight |
| Conductor Shield | Inner Layer | Outer Layer |
| mm² | No. | mm | mm | mm | mm | N | kg/km |
| 3-Layer 25kV AAC/XLPE/HDPE |
| 25 | 6 | 0.70 | 3.18 | 3.18 | 20.1 | 3762 | 356 |
| 35 | 6 | 0.70 | 3.18 | 3.18 | 21.1 | 5177 | 404 |
| 50 | 6 | 0.70 | 3.18 | 3.18 | 22.2 | 7011 | 461 |
| 70 | 12 | 0.70 | 3.18 | 3.18 | 23.9 | 10354 | 555 |
| 95 | 15 | 0.70 | 3.18 | 3.18 | 25.7 | 13727 | 664 |
| 120 | 15 | 0.70 | 3.18 | 3.18 | 26.9 | 17339 | 755 |
| 150 | 15 | 0.70 | 3.18 | 3.18 | 28.6 | 21033 | 864 |
| 185 | 30 | 0.70 | 3.18 | 3.18 | 30.2 | 26732 | 997 |
| 240 | 30 | 0.70 | 3.18 | 3.18 | 32.5 | 34679 | 1203 |
35kV SAC Cable
| Nominal Size | Min. No. of Wires | Covering Thickness | Cable Diameter | Min. Breaking Load | Weight |
| Conductor Shield | Inner Layer | Outer Layer |
| mm² | No. | mm | mm | mm | mm | N | kg/km |
| 3-Layer 35kV AAC/XLPE/HDPE |
| 25 | 6 | 0.70 | 4.45 | 3.18 | 22.6 | 3762 | 439 |
| 35 | 6 | 0.70 | 4.45 | 3.18 | 23.6 | 5177 | 491 |
| 50 | 6 | 0.70 | 4.45 | 3.18 | 24.7 | 7011 | 552 |
| 70 | 12 | 0.70 | 4.45 | 3.18 | 26.4 | 10354 | 652 |
| 95 | 15 | 0.70 | 4.45 | 3.18 | 28.2 | 13727 | 768 |
| 120 | 15 | 0.70 | 4.45 | 3.18 | 29.4 | 17339 | 864 |
| 150 | 15 | 0.70 | 4.45 | 3.18 | 31.1 | 21033 | 980 |
| 185 | 30 | 0.70 | 4.45 | 3.18 | 32.7 | 26732 | 1119 |
| 240 | 30 | 0.70 | 4.45 | 3.18 | 35.0 | 34679 | 1334 |