• PRODUCTS

Aerial Insulated Cable (IEC 60502-2)

Conductor: Circular compressed aluminum, aluminum-alloy, copper.

Conductor shield: Semi-conducting cross-linked polyethylene.

Insulation: Cross-linked polyethylene (Natural)

Sheath: PE & XLPE

Package : Export wooden drum & iron wooden drum or as customer require
Phone: +8613204662621
WhatsApp: +8613204662621
E-mail: yongbencable@163.com
Contact Us

- // PRODUCT DETAILS // -


Cable Application:

Aerial Insulated Cables with voltages of 10kV.The products primarily used for the distribution of electrical energy under normal conditions of overhead (aerial) installations.The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer etc.

Description

The conductors are stranded,circular compressed aluminum, aluminum-alloy, copper. The conductor screen is the extruded Semi-conducting conductor shield in Black. And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
SPECIFICATION :

GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV

TypeNo. of CoresNominal size
mm²
CU/XLPE,AAC/XLPE,AAAC/XLPE110 ~ 400
325 ~ 400
3+k(A) or 3+k(B)25 ~ 400 ; k:25~120
CU/PE,AAC/PE,AAAC/PE,CU/XLPE,AAC/XLPE,AAAC/XLPE110 ~ 400
AAC/XLPE,AAAC/XLPE325 ~ 400
3+k(A) or 3+k(B)25 ~ 400 ; k:25~120
The k is a load-bearing core. (A) means steel carrying stranded wire, (B) means aluminum alloy carrying stranded wire.
Parameter-Copper Conductor :
10kV Aerial Insulated Cables
Nominal SizeMin. No.
of Wires
Approx. Diameter of ConductorMin.
Thickness of Conductor screen
(Approx.)
Nominal Thickness of InsulationNominal Thickness of Insulation ScreenMin. Breaking Load
ReducedNominalHard CopperSoft CopperHard Copper
mm²No.mmmmmmmmΩ/kmΩ/kmN
1063.80.5-3.4-1.830-
1664.80.5-3.4-1.150-
2566.00.52.53.40.7490.7278465
3567.00.52.53.40.5400.52411731
5068.30.52.53.40.3990.38716052
701210.00.52.53.40.2760.26823461
951511.60.62.53.40.1990.19331759
1201813.00.62.53.40.1580.15339911
1501814.60.62.53.40.128-49505
1853016.20.62.53.40.1021-61846
2403418.40.62.53.40.0777-79823
3003420.60.62.53.40.0619-99788
4005323.80.62.53.40.0484-133040
Parameter-AAC AAAC Conductor :
10kV Aerial Insulated Cables
Nominal SizeMin. No.
of Wires
Approx. Diameter of ConductorMin.
Thickness of Conductor Screen
(Approx.)
Nominal Thickness of InsulationNominal Thickness of Insulation ScreenMin. Breaking Load
ReducedNominalAACAAACAACAAAC
mm²No.mmmmmmmmΩ/kmΩ/kmNN
1063.80.5-3.43.0803.574--
1664.80.5-3.41.9102.217--
2566.00.52.53.41.2001.39337626284
3567.00.52.53.40.8681.00751778800
5068.30.52.53.40.6410.744701112569
701210.00.52.53.40.4430.5141035417596
951511.60.62.53.40.3200.3711372723880
1201813.00.62.53.40.2530.2941733930164
1501814.60.62.53.40.2060.2392103337706
1853016.20.62.53.40.1640.1902673246503
2403418.40.62.53.40.1250.1453467960329
3003420.60.62.53.40.1000.1164334975411
4005323.80.62.53.40.07780.090455707100548
Parameter- ACSR/AW-OC :
22.9kV ACSR/AW-OC Aerial Insulated Cables
Size
(mm²)
No. and Dia.
of Wires
Conductor DiameterInsulation ThicknessCable DiameterRated
Strength
Weight
ALSt
No.No. /mmmmmmmmkgfkg/km
22.9 kV ACSR/AW-OC/XLPE
326/SB1/2.67.23.013.21090210
586/SB1/3.59.73.015.71900330
956/SB1/3.512.03.519.02360530
16018/SB1/3.215.44.023.43080730
24018/SB1/4.018.94.027.045001040